KANSAS TURNPIKE AUTHORITY

 

Leavenworth County Interchange

 

KTA CONTRACT NO. 4800

 

ADDENDUM NO. 1

 

The Contract Documents for KTA Contract No. 4800 are hereby amended in the following particulars only; all other terms and conditions remaining unchanged:

 

 

            SPECIFICATIONS:

 

DELETE:  Special Provision “TOLL PLAZA CANOPY”, Rev 04/08.

ADD:      Attached Special Provision “TOLL PLAZA CANOPY”, Rev 04/17/08

 

DELETE:  Special Provision “KTA ELECTRICAL WORK”

ADD:      Attached Special Provision “KTA ELECTRICAL WORK”, Rev 04/17/08

 

DELETE:  Special Provision “ENTRY LANE SIGN STRUCTURE/EXIT LANE

    SIGN STRUCTURE”. Rev 04/08

ADD:      Attached Special Provision “ENTRY LANE SIGN STRUCTURE/EXIT

    LANE SIGN STRUCTURE”, Rev 04/17/08

           

 

            PLANS:

 

            Plan Sheet No. 91, LIGHTING CONTROLLER “A”:

DELETE IN ITS ENTIRETY.

 

Plan Sheet No. 93, CONSTRUCTION QUANTITIES FOR ELECTRIC LIGHTING

SYSTEM: 

DELETE “Lighting Controller” item from Summary of Electric Lighting Systems

Quantities (Hardware)

 

DELETE:  ½” HEAVY DUTY REVERSIBLE DRILL item from Summary of Electric

Lighting System Quantities (Tower)

 

DELETE THE FOLLOWING NOTE:

The following companies have a raise and lowering device that has been accepted by the Kansas Department of Transportation:  American High Mast, Eagle High Mast Lighting Co., Carolina High Mast, Metrolux and Holophane.  Additional companies desiring approval by the KTA must install one raise and lowering device on a pole provided by the KTA, or on another pole as approved.

The installation will be reviewed and tested by KTA prior to approval on this project.  All associated costs will be the responsibility of the Manufacturers/Contractors.

 

REPLACE WITH THE FOLLOWING:

The raise and lowering device to be used for this contract shall be Holophane, LD5 Series Top Latch only.

 

 

Plan Sheet No. 103, TOLL BOOTH CANOPY DETAILS: 

DELETE:  the first sentence of the sixth paragraph of General Notes.

REPLACE WITH THE FOLLOWING:

The soffit lights on the underside of the canopy shall be 320 Watt, LSI Scottsdale, modular recessed luminaire, SC-S-320-PSMV-PG-MT-WHT.

 

 

Plan Sheet No. 104, TOLL PLAZA CANOPY ELECTRICAL DETAILS: 

DELETE:  the first sentence of the third paragraph of General Notes.

REPLACE WITH THE FOLLOWING:

The canopy soffit lights shall be 320 Watt, LSI Scottsdale, modular recessed luminaire, SC-S-320-PSMV-PG-MT-WHT.

 

 

Plan Sheet No. 113, ONE LINE ELECTRICAL SERVICE DIAGRAM AND DETAILS:  REPLACE existing plan sheet 113 with attachment.

 

 

Plan Sheet No. 114, POWER DISTRIBUTION PLAN PLAZA ELECTRICAL PLANS:  REPLACE existing plan sheet 114 with attachment.

 

 

Plan Sheet No. 115, PANEL SCHEDULES: 

REPLACE existing plan sheet 115 with attachment.

 

 

This Addendum No. 1 to KTA Contract #4800 is hereby made part of the Contract Documents to the same extent as if contained in the original Contract Documents.

 

Each bidder shall acknowledge receipt of this Addendum in the space provided below and shall include this Addendum as part of the Proposal.

 

                                                            ADDENDUM NO.  1  RECEIVED BY:

 

 

 

                                                            __________________________________

                                                            Authorized Signature / Title

 

 

                                                                                                                                                __________________________________

                                                            Company Name

 

04/18/08                                                                                            

                   KANSAS TURNPIKE AUTHORITY

                      SPECIAL PROVISIONS

                            TO THE

                    STANDARD SPECIFICATIONS

                        EDITION OF 2007

 

                       TOLL PLAZA CANOPY

 

 

     NOTE:     Whenever this Special Provision conflicts with the Plans, Supplemental Specifications, or Standard Specifications, this Special Provision shall govern.

 

 

1.0  DESCRIPTION:

 

     This item shall consist of furnishing and installing a Toll Plaza Canopy at the location shown on the Plans.  Installation shall include erecting and assembling the support framework, erecting the roof support beams, installing roof panels, fascia, gutter trough, downspout pipe, sign units, constructing canopy support footings, and shall include all electrical wiring and connections to the electrical panel in the equipment enclosure.

 

 

2.0  SPECIFICATIONS:

 

     A.   Canopy:  The canopy shall be designed to withstand an 80 MPH wind load and a live roof load of 30 psf.

 

          The standing seam roof panels shall be Firestone Metal Products, “Unaclad”, AWARD BLUE, Kynar 500.

 

          Subject to compliance with these specifications and approval by the Kansas Turnpike Authority, the manufacturer of canopies which may be used for this contract include is:

 

                        Arning Canopy Systems  

                        201 Industrial Park Place

                        Cassville, Missouri  65625

                        Phone: 417-847-3131

                        FAX:   417-847-3081

             

 

     B.   Fascia:  The sign fascia shall be made of 3M's Panaflex 945 signing material with vinyl graphic lamination of 3M Scotchcal Translucents.  The artwork shall be translucent vinyl laminated and plotter cut.  The sign cabinet shall be constructed of aluminum extruded framework and all rust-proof components.

 

          The sign framework shall use a spring-loaded tension system to insure the fascia will remain constant, straight, and taut.  The framework shall be built with easy access for easy maintenance of the lamps.  The fascia shall be one continuous roll and shall be fully and continuously illuminated.

 

          Fascia lighting shall be controlled with a photo-cell, and have an override switch located in the Type B Toll Booth.  The lighting shall be DHO 2 lamp continuous systems, with overlapping at the raceway intersections.

 

          The entrance and exit sides of the canopy shall have a 36" backlit Panaflex 945 sign fascia with the lines, logos, and signs as shown on the Plans.  The two (2) end fascias shall be 36" backlit Panaflex 945 with colors to match.

 

          Subject to compliance with these specifications and approval by the Kansas Turnpike Authority, manufacturers of the fascia system which may be used for this contract include, but are not limited to the following:

 

              Sharpline Converting, Inc. - Wichita, Kansas

 

     C.   Canopy Artwork:  Color, type style, and sizes for all lettering, and original artwork and colors for the "Kansas Turnpike" and "KTAG" logos are available.

 

     D.   Canopy Lighting:  The lights on the underside of the canopy shall be 320 Watt, LSI Scottsdale, modular recessed luminaire, SC-S-320-PSMV-PG-MT-WHT.  The lights shall be controlled by a photo-cell, and have an override switch in the Type B Toll Booth.  The lights shall be mounted on the canopy at the locations indicated on the Plans.

 

    


E.   Canopy Support System:  The canopy support footings shall be constructed in accordance with the canopy manufacturer's requirements.

 

          The Contractor shall supply and install 2" diameter PVC (Schedule 40) 90 degree elbows in the footings as indicated in the Plans or as directed by the Engineer.

 

     F.   Electrical Wiring & Connections:  All wiring shall conform to the National Electric Code.  The Contractor is responsible for providing connections to the electrical panel located in the equipment enclosure (see Panel Schedule Plan sheets).

 

          The Contractor shall furnish and install all electrical equipment and incidentals necessary for the satisfactory operation of the canopy lighting system prior to final acceptance by the Kansas Turnpike Authority.

 

 

 

3.0  SUBMITTALS:

 

     A.   Product Data:  Submit manufacturer's detailed technical data for materials, fabrication, and installation, including catalog cuts of anchors, hardware, fasteners, and accessories.

 

     B.   Shop Drawings:  Submit shop drawings for fabrication of canopy roof, support framework, fascia, electrical wiring and connections, and other items not fully described by product drawings.  Include plans, elevations, and large-scale sections of typical members and other components.  Shop drawings showing details of the canopy support footings shall also be submitted.

 

 

4.0  BASIS OF PAYMENT:

 

     Payment for completed and accepted work covered by this special provision will be made at the contract unit price per each for the bid item "TOLL PLAZA CANOPY".  Payment will be full compensation for furnishing, transporting, and placing all materials, and for labor, equipment, tools, and incidentals necessary to complete the work as specified and as shown on the Plans.

 

Rev. 4-17-08

     KANSAS TURNPIKE AUTHORITY

SPECIAL PROVISION TO THE

STANDARD SPECIFICATIONS

EDITION OF 2007

 

 

NOTE:  This special provision is generally written in the imperative mod.  The subject, “the Contractor” is implied.  Also implied in this language are “shall”, shall be”, or similar words and phrases.  The word “will” generally pertains to decisions or actions of the Kansas Department of Transportation.

 

 

 

KTA ELECTRICAL WORK

 

 

 


NOTE:  KTA ELECTRIC LIGHTING AND TRAFFIC SIGNALS FOR THIS PROJECT SHALL COMPLY WITH THIS SPECIAL PROVISION AND THE CURRENT ADDITION OF THE STANDARD SPECIFICATIONS:

 

 

 

1.0  DESCRIPTION

     Make arrangements for services; provide material for, and install electrical equipment IN the equipment enclosure building; provide and install engine/generator; connect the heating and cooling equipment; provide and install circuits for toll plaza; connect the electrical equipment in the prefabricated tollbooths and canopy; provide and install KTA roadway lighting as shown in the Contract Documents; perform all other electrical work necessary to complete the electrical installation ready for use; and provide and install telephone service.

 

 

BID ITEM                                              UNIT

Roadway Lighting                                Lump Sum

Electrical System (Entry Plaza)                      Each

Electrical System (Exit Plaza)                       Each

 

 

2.0  MATERIALS

a.  Provide materials that comply with the Contract Documents.

 

b.  The KTA will provide and install all toll collection equipment

 

c.  Raceways.  Provide conduit that is free from blisters, cracks or injurious defects of the material called for in the Contract Documents or as herein specified.  Show the raceway minimum trade size of ½ inch in the Contract Documents.

(1) Electrical Metallic Tubing:  Provide E.M.T. with compression fittings conduit for general use within the building and above the slab, size 2 inches and smaller.  Set screw fittings are not allowed.

(2) Galvanized Rigid Steel Conduit:  Provide conduit that is UL listed and complies with the requirements of ANSI Standard C80.1 “Specifications for Rigid Steel Conduit, Hot Dip Galvanized” manufactured by Allied Steelduct, Triangle, Youngstown, or approved equal.

(3) Provide hot-dip galvanized rigid steel conduit fittings fabricated in accordance with ASTM-A153 manufactured by Appleton Electric, Crouse Hinds, O.Z. Electric, Pyle-National, Russell & Stroll, Thomas and Betts, or approved equal.

(4) Liquid Tight Flexible Metal Conduit:  Provide Anaconda Type UA, Electi-Flex Type LA, or Sealtite Type UA liquid tight flexible steel conduit constructed of a flexible galvanized steel core made for continuous steel metal and an extruded PVC cover.

(5) Provide fittings with insulated throat that are UL labeled with an “O” ring assembly on each fitting manufactured by Appleton Electric, Ideal Industries, Efcor, or Thomas Betts.

(6) Rigid Nonmetallic Conduit:  Provide rigid polyvinylchloride, Schedule 40, 90° C nonmetallic conduit of the sizes indicated in the Contract Documents and that comply to the NEMA standards and is UL listed in conformity with Article 347 of the NEC.

(7) Provide conduit fittings, and cement produced by the same manufacturer, who have had at least 5 years experience in manufacturing these products.  Solvent weld all joints in accordance with the recommendation of the manufacturer.

(8) Cable Tray:  Provide and install a complete cable tray system that complies with NEMA standard VE-1 as manufactured by B-Line Systems or approved equal.  The system includes all straight trays, fittings, and related support accessory items as required for a complete installation.  Install the tray installation in conformance with the National Electric Code.

(9) Provide ladder type trays with 6 inch rung spacing for support of data cables, adequate cable bearing surface for the installed conductors and circuit conductors.  Ensure that the ladder is a double rung or box type and free of sharp edges or corners so as to protect conductor insulation.  Ensure that the aluminum ladder tray are is manufactured of alloy 6063-T6 provided in its natural finish state, welded construction and utilize “C” shaped channel siderails with flanges facing inward and the tray siderail with a radius to protect cables from damage.

(10) Ensure that the cable tray is of the size as indicated on the drawings:  Straight sections are 12 feet long; Splice plates are high strength to splice between supports; Splice hardware includes a spliced shoulder bolt which fully engages both the splice plate and the siderail; Locknuts are of the serrated flange type allowing for one wrench installation; and, Cable tray system includes all related accessory items such as dropouts, end plates and hardware.

(11)  Nonmetallic Wireways (Fiberglass):  Wireways shall be fiberglass polyester or PVC Plastic wireways manufactured by Hoffman or approved equal.  Fiberglass polyester wireways shall be extruded and fabricated to the size and shape indicated, with no holes or knockouts.  Cover is gasketed with oil-resistant gasket material and fastened with captive screws tested for corrosion resistance.  Connections are flanged, with stainless-steel screws and oil-resistant gaskets.

(12) Nonmetallic Wireways (PVC):  PVC Plastic wireways shall be extruded and fabricated to size and shape indicated, with snap-on cover and mechanically coupled connections with plastic fasteners.  Approved manufacturers include Hoffman; Lamson & Sessions – Carlon Electrical Products; Hubbell.

(13) Provide fittings and accessories including couplings, offsets, elbows, expansion joints, adapters, hold-down straps, end caps, and other fittings to match and mate with wireways as required for complete systems.  Select features, unless otherwise indicated, as required to complete wiring system and to comply with NFPA 70.

 

d.  Conductors.

     Provide insulated conductors with accessories in sufficient quantities for a complete installation. Ensure that installation is in accordance with NEC, and includes placement, splicing,

terminating, identifications, testing, and verification of each circuit and conductor.

     Provide conductors where indicated and required.  Ensure that all conductors installed in conduit underground are single conductor, 600 V. type USE, complying with IPCEA or ANSI latest specifications.  Ensure that building wiring is type THWN with NEMA Standard color braid.  Ensure that the wiring in the maintenance tunnel is multi-conductor tray cable.  No wire is to be smaller than No. 12 AWG.

     Use solderless pressure split-bolt connectors properly taped and painted with insulating varnish, for all above-ground splices in wiring where possible.  Vinyl plastic tape with dielectric rating of 100 volts per mil of thickness and minimum of three layers of half-lapped may be used in lieu of insulating compound and friction tape.

     Acceptable manufacturers are as follows or approved equal:

·        Okonite

·        Allied Wire and Cable

·        Rockbestos

·        Houston Wire and Cable

     Provide a durable marking on the outer surface of all cables or conductors at intervals not exceeding 24 inches.  Include manufacturer’s name, insulating material, conductor size, and voltage class on the marking.

 

e.  Wiring Devices.

      In finished spaces, utilized white switch and receptacle devices and white plastic nylon coverplates.  In non-finished spaces use stainless steel coverplates.

     Provide GFI receptacles with weather proof flat cover, equal to Hubbell No. GF 5362.

 

     f.  Nameplates.

     Provide laminated Acrylic or Melamine nameplates that are punched or drilled for screw mounting and engraved to show white letters on a dark-gray background for all pieces of equipment shown in the Contract Documents, and for all devices in panels.

    

g.  Panelboards.  Provide and install all panelboards where shown in the Contract Documents.  Mount the panelboard so the top is no higher than 6.5 feet above the floor.  Construction as follow:

      Provide dead front type panelboards.  Provide code gauge galvanized sheet steel cabinets  complete with hinged door, lock and two keys, with all exposed metal surfaces primed-painted and finished with two coats of light gray baked enamel, with trim as indicated on the Plans.  Include the completed typewritten circuit directory.  Ensure that all locks are keyed alike.

     Ensure that the panelboards is of such design that branch circuits may be changed without additional machining, drilling, or tapping.  Ensure the branch circuit connections provide sequence phasing with connections permanently identified on the face of the front of the panel interior.

     Ensure that the panelboards is equipped with automatic circuit breakers for branch circuit protection and has ratings as indicated.  Ensure that all single pole branches are rated 20 ampere unless indicated otherwise.

     Ensure that rigid busses for the panelboards are copper or copper alloy and are installed to provide consecutive phasing.  Provide solid neutral busses with solderless connectors, insulated from the cabinet and an ampacity equal to the ampacity of the phase fusses.  Ensure the equipment grounding bus is bonded to the cabinet, with solderless connectors and a main lug.  Ensure that all copper parts are plated to prevent corrosion.

     Ensure circuit breakers of the indicating type, that provide distinctive “on”, “off”, and “tripped” positions of the operating handle.  Provide single operating handle multi-pole breakers so designed that an overload in any one pole automatically causes all poles to open.

     Provide circuit breakers of the thermal magnetic type having inverse time delay thermal trip on overloads and instantaneous magnetic trip on short circuit.  The ambient compensation is for 60° C.  Ensure the circuit breakers are quick-break, quick-make on manual as well as automatic operation.  Ensure that each circuit breaker is independently removable without disturbing adjacent units or other bus connections and is fastened to the main bus bars with a bolt-on connection.  Ensure that all copper parts are plated to prevent corrosion.

     Ensure that all breakers 100 ampere frame and smaller have a minimum interrupting rating of 10,000 ampere, and all larger frame size breakers shall have a minimum interrupting rating of 22,000 amperes.

     Provide cabinets of sufficient size to provide gutter space no less than that required by the Underwriter’s Laboratories and in no case less than 4 inches.

     Provide panelboards that are factory assembled, UL listed, type NQOD for 240 volts and NF for 480 volts manufactured by Square D only.

 

h.  Standby Engine Generator Set. 

(1) General:  Provide a Propane fueled engine-generator sets as shown in the Contract Documents.

(2) Ratings:  Ensure that the engine-generator set is a 4 cycle, 1800 rpm, high ambient cooling system, with low reactance brushless generator, torque-matched excitation, automatic voltage regulator, set mounted control panel, and fully rated for standby, 120/240 volt AC, three phase, four wire, 60 hertz.

(3) Generator:  Ensure that the voltage regulation is + 0.5 percent of rated voltage for any constant load between no load and rated load and capable of single step load pick up of 100% nameplate.

Ensure that the generator is:  synchronous, four pole, revolving field, drip-proof construction; single pre-lubricated sealed bearing; air cooled by a direct drive centrifugal blower fan; and, directly connected to the engine with flexible drive discs.  Ensure that all insulation system components meet NEMA MG1 standard temperature limits for Class H insulation system.  Ensure that the actual temperature rise measured by resistance method at full load does not exceed 257°F. (125°C).

Provide a Shunt excitation system that uses power from the main generator output.  Ensure that the automatic voltage regulator has temperature compensated, half wave phase controlled solid state design and includes an under-speed protection function.  Ensure that the regulator design includes a torque-matching characteristic to allow the engine to use its fullest power producing capability at speeds lower than rated, to optimize motor starting capability and to provide the fastest possible recovery from transient speed dips.

Ensure that the generator is an extended stack type to provide three-phase output.

(4) Control:  Ensure that the control has automatic remote start capability from a panel-mounted 3 position (Stop, Run, Remote) switch.  Provide cycle cranking of 15 seconds on /15 seconds off for three attempts.  If engine fails to start, lockout engine and indicate over-crank on alarm status panel.  Ensure that the control shuts down and locks out upon:  failing to start, over-speed, low lubricating oil pressure, high engine temperature, or operation of a remote manual stop.  A panel mounted switch resets the engine monitor and test all the lamps.  Ensure that the lamps on the control panel lamp indications include:

Over-crank shutdown – red

Over-speed shutdown – red

Low oil pressure shutdown – red

High engine temperature shutdown – red

High engine temperature pre-alarm – yellow

Low engine oil pressure pre-alarm – yellow

Low coolant temperature – yellow

Low fuel - yellow

              Run – green

              Not in automatic start – flashing red

 

Ensure that the enclosed control panel is mounted on the generator set with vibration isolators.  Provide a front control panel illumination lamp with ON/OFF switch.  Ensure that the control panel mounted indicating meters and devices include:  Engine Oil Pressure Gauge, Coolant Temperature Gauge, DC Voltmeter, and Running Time Meter.

Ensure the AC voltage meter package includes analog AC voltmeter, analog AC ampmeter, analog frequency/RPM meter, analog power factor meter, and analog wattmeter.

(5) Engine:  Ensure that the engine is a 4 cycle, 1800 RPM, with forged steel crankshaft and connecting rods and a cast iron block and two valves per cylinder.  Two cycle engines are not acceptable.

Ensure that the mechanical governor, integral with the fuel pump, provides automatic engine-generator set frequency regulation of 5% drop.

Ensure that the engine is cooled by a unit-mounted closed loop radiator system rated for full rated load operation in 122°F. ambient.  Fill the engine cooling system with a 50/50 ethylene glycol/water mixture.  Shield all rotating parts against accidental contact.

Provide the following accessories with the engine-generator set:

(5.1) Starter:  An electrical starter capable of three complete cranking attempts without overheating.

(5.2) Oil Pump:  Positive displacement, mechanical, full pressure, lubrication oil pump.  Full flow lubrication oil filters with replacement spin on canister elements and dipstick oil level indicator.

(5.3) Charger:  Engine mounted battery charging alternator, 45 ampere, and solid-state regulator.

(6) Base:  Ensure that the set is mounted on a heavy duty steel base to maintain alignment between components.  Incorporate in the base, a battery tray with battery holddown clamps within the rails.  Ensure that provisions for stub up of electrical conduits are within the footprint of the set.  Ensure that vibration isolators, standard quality and type are integral between generator set and base.

(7) Auxiliary Equipment:  Ensure that the engine-generator set includes the following accessories:

(7.1) Main Circuit Breaker:  Ensure that the generator main circuit breaker is set mounted and wired, UL listed, molded case thermal-magnetic type, rated 240 volts, 3 pole.

(7.2) Batteries:  Supply starting batteries, lead acid type, size as recommended by the manufacturer for each generator set with battery cables and connectors.

(7.3) Charger:  Ensure that a 10 amp voltage regulated battery charger is provided for the engine-generator set.  Ensure that the input AC voltage and DC output voltage is as required.  Provide visual output indicators for operational monitors of:

Loss of AC power – red

Low battery voltage – red

High battery voltage – red

Power ON – green

(7.4) Muffler:  Ensure that the engine muffler is provided as recommended by the manufacturer.

(8) Automatic Transfer Switches:  Provide transfer switches with electronic control designed for surge voltage isolation, voltage sensors on all phases of both sources, linear operator, permanently attached manual handle, positive mechanical and electrical interlocking, mechanically held contacts, quick make, quick break contact mechanisms for transfer under load.

(8.1) Ratings:  Ensure that the switch is UL listed and labeled, tested per UL Standard 1008, and CSA approved.

Provide switches that are 3 pole, 240 volt with 600 volt contacts and carry a rating of 100 percent of the rated current continuously in a temperature range of -40° C. to +50° C.  Ensure that the switch has a “withstand” and “closing” rating in RMS symmetrical amperes greater than the available fault currents shown on the drawings.

(8.2) Automatic Controls:  Provide controls that are solid-state and designed for a high level of immunity to power line surges and transients, demonstrated by test to IEEE Standard 587-1980.  Ensure that the controls have optically isolated logic inputs, high isolation transformers for AC inputs, and relays on all outputs.

Provide solid-state under-voltage sensors that simultaneously monitor all phases of both sources; the voltage sensors allow for adjustment to sense partial loss of voltage on any phase; and, the voltage sensors have field calibration of actual supply voltage to nominal system voltage.  Ensure that pick-up and drop-out settings are adjustable.

(8.3)  Front Panel Devices:  Provide devices mounted on cabinet front consisting of a three position selector switch to provide the following functions:

·         Test – simulates normal power loss for testing generator set.

·         Normal – Normal operating position

·         Retransfer – Momentary position to override retransfer time delay and cause immediate return to normal source.

Manufacturer:  Provide engine generator and automatic transfer switches made by the same manufacturer and provided by Onan Corp.

 

i.    Grounding.

Provide stranded soft-drawn, insulated copper ground cable that complies with ASTM B3

Class B.  Ensure that ground cables are interconnected or bonded to structural steel or ground rods by exothermic welds.  Apply two coats of insulating varnish over all exothermal welds and exposed cables.

      Provide ground rods that are ¾ inch x 10 foot copper clad standard type, as manufactured by Copperweld, Weaver, or approved equal.

 

j.    High Mast Roadway Lighting.

(1)  1000 Watt High Mast Lighting:  Provide 1000 watt high mast luminaries with a housing of a single piece, copper free aluminum alloy casting; arm attachment clamp that engages a 2 inch nominal pipe and allows 3 degree adjustment for leveling; and, all ballast components that are mounted to a single plate which are removable, with a quick disconnect plug, as a unitized assembly for maintenance.  Ensure that the symmetrical distribution reflector is borosilicate glass and is specially made to reduce direct glare.  Provide luminaries manufactured by Holophane Only, Cat. #HMSD-C10HP-48-S8-PS-ELB.

(2)  High Mast Towers:  Provide towers that are completely galvanized in accordance with the requirements of ASTM A-123 and comply with the requirements of ASTM A-595 with the exceptions and/or additions as listed in the Standard Kansas Department of Transportation Standard Specifications, 2007 Edition, Section 1608.  Ensure that the tower assembles by telescoping on the job site. 

(3) Base Plate:  Provide base plates made of steel plate that have essentially the same chemical composition as the tower and are designed to withstand the full bending moment of the shaft.

(4) Main Support Assembly:  Provide the main support assemblies fabricated from weldable structural steel, hot dipped galvanized in accordance with ASTM A 123 or electroplated with a minimum thickness of 0.4 mil, and attached to the shaft by sleeving and secured by set screws or other similar attaching means.  Ensure that the main support assembly has six hoisting sheaves and one power cable sheave.  Ensure that the sheaves are oil impregnated, sintered bronzed bushings over stainless steel shaft, or permanently sealed ball bearings with inner fixed races.  Include mechanical latching devices in the main support assembly.

(5) Luminaire Ring:  Provide luminaire rings constructed of weldable structural steel, hot dipped galvanized in accordance with ASTM A 123 or electroplated with a minimum thickness of 0.4 mil with three or four, as required, 2-inch nominal steel; pipe luminaire mounts.

 

k.    Conventional Roadway Lighting.

(1)  Roadway Luminaire:  Provide luminaries that are high-pressure sodium type, 250 watt rating that have a “cobra head” shape with cast aluminum housing, stainless steel external hardware, lens holder with latch, sealed and gasketed flat glass lens, 2 inch diameter end mounting slip fitter, external mounted light distribution decal, an adjustable glazed porcelain lamp socket, and a lamp vibration end support grip.  Roadway luminaire shall be Thomas & Betts, American Electric 125 series single door cutoff 126-0-66-3-3-DJ-0-0-A-0 or approved equal.

(1.1) Ballast:  Ensure that the ballast is the integral isolated magnetic regulating type with a 10% line voltage variation that give wattage regulation as prescribed by the trapezoidal limits in ANSI Standards for a high pressure sodium lamp throughout the rated life of the lamp.  Ensure that the lamp igniter is designed and tested to operate continuously for 800 hours in a 194°F (90°C) ambient environment.

(1.2) Housing:  Ensure that the entire luminaire assembly is constructed and equipped to withstand high shock and vibration.  Ensure that the luminaire with lamp successfully pass vibration testing consisting of 3 g. forces for 100,000 cycles at the resonant frequencies in each of the three planes.  Submit the test reports before approval of the luminaire.

(1.3) Distribution:  Provide factory set luminaries that produce the IES Type III distribution.  Supply published data obtained from photometric tests conducted according to IES testing procedures.

(1.4) Grounding:  Ground each luminaire by a green insulated no. 12 AWG copper conductor attached to the luminaire housing and to the grounding lug a the base of the light standard.

(2) Lighting Pole Foundations:  Provide cast-in-place, concrete, drilled shaft foundations for the ground-mount, lighting.  Complete the foundations to include anchor bolts, anchor nuts, shim pack, reinforcing, ground leads, and 2 inch diameter PVC entrance conduits.

 

     

      l.  Special Systems.

(1)Install Overheight Detection Equipment, designed to warn booth operators of vehicles

that are too tall,  as indicated on the plans.

(2)Photoelectric Controls: Provide the photoelectric control that is an outdoor unit that

fits in a standard watt-hour meter socket, attached to a 1 inch galvanized rigid conduit, anchored to the equipment enclosure. Ensure that the control operates on 105-130 V.A.C., 60 Hertz. Ensure that the control is designed to energize system upon failure.

(3)            Axle Counting Treadles:  Install 2 inch galvanized rigid steel conduit to treadle frames, provided by the KTA.  Treadle Frames are to be installed as a part ofthe bid item “Toll Plaza”.

      (4)  Install all conduits of the size and type specified to the Entry Lane and Exit Lane Sign Structure.  Pull all conductors and provide all connections for a complete and working system of signs for the sign structures with switch controls in the Type B Booth.

      (5)  Install all conduits of the size and type specified in the ETC Installation Details.  Where conduits are cast in concrete paving, coordinate all work with the paving contractor.  Where conduits, junction boxes or other equipment is cast into service pads, include the placement of these service pads in the installation.

(6)             Temporary Power Service:  Provide temporary power service if found to be needed, and remove it upon connection to the permanent system.

    

m.  Basis of Acceptance.

      The Engineer will accept the roadway lighting and accessories, and electrical system on the basis of approved catalog cuts and satisfactory completion of the work.

 

 

3.0 CONSTRUCTION REQUIREMENTS

      a. Install the electrical system as shown in the Contract Documents.

 

      b. Make all contacts with Kansas Power and Light and all necessary scheduling of work with the utility.  The Electrical Contractor shall pay costs associated with concrete pads and conduits to set pad mounted equipment.  All hook-up and other fees charged by the utility shall be direct billed to the KTA.